Run the grid

At 12:33 on 28 April 2025, Spain and Portugal went dark in seconds. A power grid has to match supply and demand every second, and hold its in a narrow band while it does it. Can you keep the lights on?

Electricity demand, peninsular SpainREE, 5‑min data
Monday 28 April 2025 (teal) against Tuesday 22 April, a normal spring weekday (grey). Demand is what consumers drew, served from the grid. Source: Red Eléctrica.

Start here · two minutes

The grid in six ideas

Everything on this page rests on six ideas. None needs any maths. Each one has a small thing to tap or drag.

Idea 1

Supply must match demand, every second

The wires store almost nothing. Every second, power stations must produce exactly what homes, offices and factories use. On a normal spring day, peninsular Spain used between 20 and 32 GW (a gigawatt is 1,000 megawatts, about what one large power station makes). REE data

Generation25.0 GW
Idea 2

Frequency is the grid's heartbeat

Alternating current swings back and forth 50 times a second, and every big generator spins in step with it. Use more power than is produced and the generators slow down, so frequency falls. Produce too much and it rises. Normal is within ±0.2 Hz of 50. ENTSO-E

50.00 Hz
Idea 3

Inertia: the grid's flywheel

Spinning generators (nuclear, gas, hydro) store energy in their heavy rotors. When a plant suddenly trips, that stored energy slows the fall in frequency and buys seconds for reserves to react. Solar panels and most wind turbines connect through electronics and don't add any.

Same loss, two real moments from REE's data.
Idea 4

Voltage is pressure, and it's local

Frequency is one number for the whole grid. Voltage differs from place to place, like water pressure in different streets. It is pushed up or down mainly by : injecting it raises nearby voltage, absorbing it lowers it. Spain's main grid must stay between 380 and 435 kV. GOV

Town Babsorb ← → inject
Idea 5

Protection: plants disconnect to save themselves

Every plant and line has relays that disconnect it if voltage or frequency goes beyond set limits, to avoid damage. Plants are required to stay connected (ride through) within set ranges, so their protection shouldn't trip them sooner. The danger is a chain: if one disconnection makes things worse, the next plant goes, then the next. That's a cascade.

Idea 6

Spain is wired into Europe

AC lines to France tie Spain and Portugal into one synchronous grid with continental Europe, all turning at the same 50 Hz. A to France and an AC link to Morocco carry power too. GOV Europe's size steadies them. If the links are cut, Iberia becomes an island on its own. That happened at 12:33:21 on 28 April.

Connected: Europe shares any imbalance.
FrequencyVoltage
What it isHow fast the current swings back and forthThe electrical pressure on a line
WhereOne number for the whole connected gridDifferent at every substation
Set byReal power: generation vs demand (MW)Mainly reactive power: injected vs absorbed (Mvar)
Normal50 Hz, within ±0.2380–435 kV on Spain's 400 kV grid
28 AprilAbout 50 Hz until the last secondsThis is what failed first

Level 1 · a normal day

Balance Spain's grid for 24 hours

This is Tuesday 22 April 2025, a normal spring weekday, with REE's real demand, solar and wind for every 5 minutes. You run the five things an operator can move: nuclear (slow), gas, hydro, pumped storage and interconnections. Keep supply equal to demand and stays at 50 Hz. Fall short and it sags; too far and protection starts cutting customers off.

00:0022 April 2025
Normal
50.000 Hz
Short of demand0 MWSurplus
0.000, Hz/s
–Inertia H, s
0%Reserve used
Your generation mix, GWline: demand + pumping + exports
Press play. Demand, solar and wind follow REE's real data; the sliders are yours.

The day runs about 600 times faster than real life; the frequency physics runs at real speed. Spain is treated as an electrical island, which is what it became at 12:33:21 on 28 April. In real life it is tied to the rest of Europe, which shares out any imbalance. A simplified teaching model, not a grid study: see how it works.

What happens as frequency falls

The lesson

Same loss, different grid: what inertia buys you

When a power plant trips, the first thing that happens is that every spinning machine on the grid slows a little, handing over some of its stored energy. The more energy is spinning, the slower falls, and the more time automatic reserves have to catch it. Pick two real moments from REE's data and drop the same plant out of both.

Grid A

Grid B

Two things this does not mean. Inertia sets how fast frequency falls, not whether it recovers: that is the reserves' job. And it was not what failed on 28 April. The cascade began with frequency at about 50 Hz, and the final report's simulations found that even with significantly higher inertia values, the loss of system synchronism would not have been avoided. FINAL

The other gauge

Voltage: the problem on 28 April

Frequency is one number for the whole grid. is local, and it is set by . Anything that injects reactive power pushes nearby voltage up; anything that absorbs it pulls voltage down. On 28 April too little was absorbing, and it wasn't fast enough. Try the levers the operator and the rules controlled that morning.

400 kV grid, south‑west (illustrative)Normal
415 kV

Bars: reactive power in Mvar, injected (right) or absorbed (left). The directions are what the reports describe; the sizes are illustrative, not calibrated to the Spanish grid.

Extra 400 kV circuits in service10

Lightly loaded lines inject reactive power. REE connected 10 circuits after 11:10 to damp the oscillations. GOV

Shunt reactors switched in5

Each absorbs Q = B·V². Switched by hand: out when voltage was low at noon, five back in by 12:28. GOVFINAL

Synchronous plants absorbing

Units with a voltage duty had to follow a reactive reference; several reached it in under 75% of samples. FINAL

Renewables' reactive mode

At fixed power factor, absorption is tied to output. In voltage‑control mode, allowed since June 2025, it follows voltage. FINALCNMC

Renewable output in the area100%

Large plants cut about 500 MW between 12:32:00 and 12:32:48. Watch what fixed power factor does when output falls. FINAL

Trip a plant absorbing 165 Mvar

Granada, 12:32:57: it was absorbing 165 Mvar, and when it tripped, the absorption went with it. FINAL

Why trips made it worse: each plant that disconnected on overvoltage took its reactive absorption with it, so the voltage rose again, tripping the next. Load shedding then removed reactive load too, raising voltage further. FINALARXIV The replay below shows it happening, second by second.

The blackout replay

28 April 2025: ninety seconds, in slow motion

It was not a lack of power. Spain was exporting about 4.3 GW to its neighbours at 12:30. It was voltage: it climbed across the grid, plants disconnected to protect themselves, and every disconnection pushed voltage higher. Only at the end did frequency collapse. Every value below comes from the official reports, tagged with its source.

The grid at 12:30

A sunny Monday with very cheap power: the day‑ahead price averaged €18.50/MWh and was zero or negative in the middle hours GOV. Solar supplied more than half of the electricity. Pumped‑storage plants were using the surplus to pump water uphill.

Generation in peninsular Spain at 12:30, 28 April 2025, from REE's 5‑minute data. Hydro is conventional hydro; pumping and exports are where the surplus went. machines spin in step with the grid and carry ; solar PV and wind connect through .

The morning: oscillations, and a cure with a side effect

Two bouts of shook the grid around noon. The operator, Red Eléctrica (REE), damped them with standard tools: more lines in service, lower exports, a fixed setting on the link to France. Every report agrees on the side effect: those measures raised voltages.

Oscillation Operator action Voltage-control gap
  1. 19:47 (27th)
    One south‑west thermal unit scheduled for drops out. It is not replaced for the midday hours. GOV On the morning of the 28th REE concluded that it was not necessary to replace it. FACTUAL
  2. 06:00
    Export schedule to France cut from 2,590 MW to 1,600 MW. GOV
  3. 09:00–10:30
    Voltage variability grows, with larger swings from 10:30. Voltages stay inside the Spanish 400 kV band of 380–435 kV. Small 0.2 Hz oscillations come and go through the morning (05:49, 08:52, 10:30, 11:06, 11:23). GOV
  4. 11:08–11:20
    Three 400 kV circuits connected to improve . GOV
  5. 12:03
    Oscillation 1, at 0.63 Hz, until 12:08. FINAL classes it as a local, converter‑driven phenomenon, most active between Carmona and Almaraz. Voltage swings of over 30 kV peak‑to‑peak at Almaraz and Arroyo de San Serván. GOVFINAL
  6. 12:04–12:25
    With voltages briefly low, operators switch out: Villaviciosa, Guadame, Rueda, Aragón, then Cabra, Peñaflor, Palos, Morata. Seven more 400 kV circuits are connected. GOV
  7. 12:07–12:20
    Exports to France cut again, to 1,500 then 1,000 MW. At 12:11 the link to France is switched from AC‑emulation to a fixed 1,000 MW export, held until the collapse. GOV
  8. 12:19
    Oscillation 2, at 0.2 Hz, until 12:22: the East–Centre–West mode that swings the whole continental grid. GOVFINAL
  9. 12:26
    REE orders a voltage‑controlling thermal unit in the south. The fastest available needs 1 h 30 min to connect, so it is scheduled for 14:00. It never connects. Reactors go back in as voltages rise. GOV
  10. 12:30
    Voltages 410–420 kV; frequency about 50 Hz; low damping. GOV

12:32:00 to 12:33:30

Press play. The first minute runs fast. The last fifteen seconds run at a third of real speed, because that is when everything happens. Tap any event to jump to it.

Time (CEST)
12:32:00.000
Generation lost
0 MW
Highest voltage reported
413 kV
Frequency
≈50.0 Hz
paused
Voltage at a tripping element (different substations) Frequency, reported values joined Generation lost

The time axis is broken: the left third covers 75 seconds, the right two‑thirds the last 16. Each voltage dot is a value reported at a different place, so the dots are not one continuous trace. Frequency is about 50 Hz until the AC link to Europe starts to slip; the official reports give exact values only from 49.5 Hz down.

Level 2 · what if?

Could anything have stopped the cascade?

These are the changes the reports discuss, each labelled with how confident they are. Switch any on and rerun the last 90 seconds in a toy version of the voltage model above. The toy is tuned to show the reports' reasoning: it can illustrate their conclusions, not test them. The verdict that counts is the reports' own, under the chart.

Toy rerun, 12:32:00 to 12:33:30
Toy with your leversDashed: toy with noneA plant group trips

    After 12:33

    Bringing a country back from zero

    A dead grid can't simply be switched back on: power stations need power to start. Operators built small islands of supply and grew them. They started from the lines to France (Catalonia, the Basque Country) and Morocco (the south), and from hydro plants in the Duero, Galicia and Asturias‑Cantabria. Then they joined the islands together. Some attempts failed and had to be repeated. GOVFINAL

    28 Apr 12:30

    Demand served in peninsular Spain, REE 5‑minute data (teal), against the same hours of Tuesday 22 April (grey). Milestones from the government report and ENTSO-E. Portugal's are in the list. REE data

      Myths vs evidence

      What didn't cause it, and what's half true

      A cyberattack no evidence

      The government ran what the minister called the largest cybersecurity investigation in the country's history. It found no evidence of cyber-incident or cyber-attack, though it did find vulnerabilities. GOV

      A rare "atmospheric vibration" false

      Portugal's grid operator REN denied ever issuing the statement. The weather agency AEMET found no unusual phenomena. EDMO traced the claim to a deleted press alert. REN · AEMET · EDMO

      Too much solar half true

      ENTSO-E's president: It's not about renewables, it's about voltage control. But most units that tripped were inverter‑based, and the fixed power‑factor rule made renewables amplify the voltage rise. It was the rules and settings, not the solar share: on 22 April solar was 51% at 12:30, and nothing happened. POWERFINALMaldita

      Low inertia not the cause

      Inertia was above ENTSO-E's recommendation, and the cascade started with frequency at about 50 Hz. The final report's simulations: higher inertia alone would not have avoided the loss of synchronism. REEFINAL

      More nuclear would have saved it not automatically

      3,078.6 MW of nuclear was declared unavailable (refuelling or maintenance); four reactors were connected. Synchronous units, nuclear included, were among those that didn't meet their reactive reference. Spinning machines only help voltage if they absorb reactive power. GOVFINAL

      Three readings

      Who's to blame? The reports agree on the physics, not the fault

      Every official report calls it a multifactorial overvoltage: not enough dynamic voltage control, oscillation fixes that raised voltages, and disconnections, some of them improper. Who should have absorbed more is still disputed. Here are the positions side by side. This page doesn't pick a winner.

      ENTSO-E Expert Panel final report, 20 Mar 2026

      • The key phenomenon was that voltage control in Spain was not effective. Renewable plants ran at a , so as their output fell, so did the reactive power they absorbed. FINAL
      • Several large synchronous generators reached their reactive‑power reference in less than 75% of hourly samples. Shunt reactors were switched by hand. Some protection settings were below the requirements. FINAL
      • Simulations: increased reactive power margins could have prevented system collapse. The report says it does not assign liability. FINAL

      Spanish government committee 17 Jun 2025

      • Not enough dynamic voltage control: units either weren't scheduled, didn't deliver what the rules required, or both. GOV
      • REE scheduled 10 thermal units for voltage control; one south‑west unit dropped out the evening before and was not replaced. GOV
      • Some disconnections were apparently improper. No evidence of a cyberattack. GOV

      Red Eléctrica (REE) grid operator

      • Generators with voltage‑control duties under the operating rule failed to comply with them. REE
      • Its scheduling was sufficient; inertia was above ENTSO-E's recommendation. REE
      • On the final report: Red Eléctrica no falló; REE says the panel does not name its scheduling as a cause. REE 2026

      The utilities (AELEC) Iberdrola, Endesa, EDP

      • REE alone was responsible: it chose to manage voltage with limited synchronous capacity, unevenly spread across the country. AELEC
      • Their plants met the rules. Voltage swings fell 37–52% in the days after, once more gas plants ran. AELEC
      • Endesa's CEO: the central cause was REE scheduling un número reducido de grupos able to control voltage dynamically. El Español

      The final report adds a third party to the story: the rules themselves. Fixed power factor for renewables, a 435 kV operating limit with little margin below generators' 435–440 kV ride‑through limits, and no economic penalty for missing reactive targets. FINAL The regulator, CNMC, has since let renewables provide voltage control (June 2025) and added a simpler fixed‑setpoint mode (July 2026). CNMC

      Method

      How this page works

      This is a simplified teaching model, not a grid study. The game and the comparisons use one aggregated machine for all of peninsular Spain. The replay is different: it is the record from the official reports.

      The replay is the record, not a simulation

      Every time, value and place in the replay comes from the official reports: millisecond timestamps from the Spanish government committee (GOV), causes and the generation‑loss totals from the ENTSO-E Expert Panel (FACTUAL and FINAL). Where they disagree, the event card says so. The chart joins reported frequency values with straight lines; it is not a measured trace. Voltage dots are values at different substations and are not joined.

      The numbers at 12:30 are REE's own data

      Demand and the generation mix come from REE's public 5‑minute data for peninsular Spain, retrieved on 16 October 2026 and embedded in this page. REE's 12:30 demand, 25,184 MW, matches the government report exactly. REE's hydro figure is net of pumping, so conventional hydro is shown as hydro plus pumping, which reproduces the government report's shares (solar 54%, nuclear 10%, gas 3%). "Other" is coal, cogeneration, biomass and the small remainder REE does not break out.

      Level 1: the frequency model

      Frequency follows the aggregated : a mismatch between generation and load speeds up or slows down every synchronous machine at once, and the stored spinning energy sets how fast.

      df/dt = (Pgen − Pload) · f0 / (2 · Ekin)    Ekin = Σ Hi · Si

      f0 is 50 Hz, P is in MW and Ekin in MW·s. Only synchronous machines count towards Ekin: nuclear, gas, coal and cogeneration, solar thermal, hydro and pumped storage, in both pumping and generating mode. Solar PV, wind and imports add none. Each step of the game also adds automatic reserves, load that falls slightly with frequency, and the protection steps listed under the game.

      ParameterValueSource
      Demand, solar PV, solar thermal, wind, other thermalREE 5‑minute values for 22 April 2025REE data
      Inertia constant Hnuclear 6 s; gas, coal, cogeneration, solar thermal 4 s; hydro and pumped storage 3 sPicked inside Kundur's typical ranges (thermal 2.5–10 s, hydro 2–4 s) Kundur
      Rating vs output, S / P1.29 for all synchronous unitsCalibrated so 12:30 on 28 April gives H = 2.3 s NREL, inside the 2.21–2.71 s range ARXIV
      Automatic reserve (FCR)1,500 MW, fully deployed at ±0.2 Hz, 5 s responseassumption The ±0.2 Hz and 30‑second rules are ENTSO-E's ENTSO-E; the size for an islanded Spain is not published
      Load self‑regulation1.5% of load per 1% of frequencyKundur's typical 1–2% Kundur
      Over‑frequency response (LFSM‑O)solar and wind cut output above 50.2 Hz, 5% droop50.2 Hz from ENTSO-E ENTSO-E; 5% droop assumption (EU default)
      Pumping shedhalf at 49.5 Hz, the rest at 49.3 HzThresholds GOV; the half/half split assumption
      Load shedding49.0, 48.8 … 48.0 Hz; 5% of demand, then 8% per step to 45%Steps GOV; shares NC ER; reconnection above 49.8 Hz SAFA
      Blackoutbelow 47.5 Hz or above 51.5 HzGenerator withstand limit GOV; upper frequency range for generators RfG
      Gas startnew capacity online 90 minutes after you askThe hot start REE was quoted on 28 April GOV
      Capacity limitsgas 17,136 MW; nuclear 4,038 MW; pumped generation 3.3 GWInstalled minus unavailable on 28 April GOV (22 April availability not published)
      Hydro, pumping and exchange limits10 GW; 3.2 GW pumping; ±5.5 GWAbout the extremes in REE's data for these days REE data
      Ramp ratesnuclear 8, gas 150, hydro 250, pumped storage 300, exchanges 400 MW per minuteJust above the fastest 5‑minute change in REE's real dispatch that day REE data, so the real schedule is feasible. Plant ramp limits were not in the research
      Surprise trip1,000 MW of nuclear at 13:30hypothetical Nothing tripped on 22 April

      The inertia comparison

      The same island model as Level 1, run for 20 seconds after a single loss, on two real moments from REE's data. The spinning energy of each moment comes from its real mix, with the same inertia constants and calibration.

      The voltage panel and the what‑if toy

      One aggregated 400 kV node: voltage = 400 kV + a sensitivity × (reactive power injected − absorbed). Shunt reactors absorb Q = B·V². Synchronous plants absorb in proportion to voltage above a 410 kV dead band (the 405–410 kV band with no obligation, ARXIV's reading of REE), at half strength "as on 28 April". Renewables absorb a fixed share of their output at fixed power factor, or follow voltage in voltage‑control mode. The Granada plant's 165 Mvar is from the final report. Every other size is illustrative, chosen so that the default sits at 417 kV (GOV: 410–420 kV at 12:30).

      The what‑if toy adds six groups of renewable plants named after the reported trips, each with an overvoltage trip setting, and a slow rise standing in for the scheduled output cuts and small losses before 12:33. Its baseline trips Granada at about 52 seconds and runs away at about 70 (real: 57 and 76). It was tuned so its levers behave as the reports reason. It cannot confirm or refute any lever. The toy's verdict is shown apart from the reports' own words.

      Restoration

      REE's 5‑minute demand for 28 and 29 April, with milestones from the government report and ENTSO-E's slides. Times are rounded to the 5‑minute grid on the chart; the list gives the reported times.

      What the model leaves out: the rest of Europe, the grid's geography and lines, voltage dynamics, automatic frequency restoration after the first 30 seconds, unit commitment, and costs. It shows why balance and inertia matter; it cannot say what any real plant would have done.

      Words used on this page

      Underlined words can also be tapped anywhere on the page.

      Sources and credits

      Every source behind this page, what it is used for and its terms. The tags on the page (GOV, FINAL, …) link here. Report figures are restated as facts with citation; no figures or images from the reports are reproduced.

      Informe no confidencial del Comité de Análisis 28-AGOV

      Gobierno de España, committee for the analysis of the 28 April crisis, approved by the Council of Ministers on 17 June 2025. Press release.

      Used for: the millisecond timeline, voltages and frequencies in the replay, the morning events, the system state at 12:30, load‑shedding thresholds and the committee's findings.

      Terms: Spanish public‑sector information, reusable under Ley 37/2007 with citation and without distorting it.

      ENTSO-E Expert Panel, Final ReportFINAL

      Grid Incident in Spain and Portugal on 28 April 2025, 20 March 2026. Panel of 49 experts from ACER, national regulators, TSOs and RCCs.

      Used for: causes, the 727 MW and 928 MW trip totals, the 0.63 Hz oscillation, the RoCoF statement, the inertia and reactive‑margin simulations, reactive‑power compliance findings. Checked against the report PDF (pages 11–22).

      Terms: reuse terms not stated; facts cited, nothing reproduced.

      ENTSO-E Expert Panel, Factual Report and briefingFACTUAL

      3 October 2025. Facts only, no root causes.

      Used for: about 525 MW of early losses, about 2.5 GW lost by 12:33:18, loss of synchronism from 12:33:19, the unit not replaced on the morning of the 28th.

      Terms: reuse terms not stated; facts cited.

      ENTSO-E, SO ESC slidesSO ESC

      System Operation European Stakeholder Committee, 4 June 2025. Preliminary.

      Used for: ENTSO-E's collapse time of 12:33:24, Portugal's load shedding.

      Terms: reuse terms not stated; facts cited.

      Red Eléctrica, incident reportREE

      Blackout in Spanish Peninsular Electrical System the 28th of April 2025, 18 June 2025, and press release.

      Used for: REE's position on compliance, scheduling and inertia.

      Terms: REE legal notice (see REE data below).

      REE, "Red Eléctrica no falló"REE 2026

      Press release, 20 March 2026, the day the final report was published.

      Used for: REE's reading of the final report.

      Terms: REE legal notice.

      AELEC (Iberdrola, Endesa, EDP)

      As reported by Ara.cat and E&T / Reuters, 2025.

      Used for: the utilities' position.

      Terms: press reports, paraphrased with short quotes.

      El Español, interview with José Bogas

      Endesa CEO, 12 February 2026.

      Used for: a short quote on REE's scheduling.

      Terms: press, short quote with attribution.

      CNMC resolutions on P.O. 7.4CNMC

      Comisión Nacional de los Mercados y la Competencia: June 2025 P.O. 7.4; DCOOR/DE/006/26 of 10 July 2026. Summary by UNEF.

      Used for: the rule changes since the blackout.

      Terms: Spanish public‑sector information, Ley 37/2007.

      Red Eléctrica, demand and generation dataREE data

      "Seguimiento de la demanda", peninsular Spain, 5‑minute values for 22, 28 and 29 April 2025, retrieved 16 October 2026 (the days are closed; REE gives no later update date for this feed). Cross‑checked against REE's REData API.

      Used for: every demand curve, the generation mix and the exports at 12:30.

      Terms: REE legal notice: may be published on a website for informational, non‑commercial purposes, naming REE as the source, without altering the data, and stating the date. Source: Red Eléctrica.

      Albustami & Taha, arXiv:2511.17433ARXIV

      "The Iberian Blackout: A Black Swan or a Gray Rhino?", November 2025. Academic analysis, not an official report.

      Used for: the inertia range at 12:30 (citing the Factual Report).

      Terms: arXiv preprint; cited, nothing reproduced.

      POWER Magazine, "Anatomy of a Blackout"

      23 March 2026, and pv magazine the same day.

      Used for: background on the final report; every figure used was then checked in the report itself.

      Terms: press, cited.

      Kundur, Power System Stability and ControlKundur

      P. Kundur, McGraw‑Hill, 1994. Table 3.2 (typical inertia constants) and chapter 11 (load self‑regulation).

      Used for: the inertia constant of each technology and the load‑damping factor in the model.

      Terms: textbook, cited.

      Regulation (EU) 2017/2196, network code on emergency and restorationNC ER

      Annex: automatic low‑frequency demand disconnection for Continental Europe.

      Used for: load‑shedding shares: 5% of load at 49.0 Hz, 45% cumulative at 48.0 Hz, at least 6 steps, at most 10% per step.

      Terms: EU law, © European Union, reuse authorised with acknowledgement.

      ENTSO-E, FCR explanatory note and LFSM guidance (NC RfG)

      ENTSO-E guidance on frequency containment reserves and limited frequency‑sensitive modes.

      Used for: the 3,000 MW reference incident, FCR fully deployed at ±0.2 Hz within 30 s, LFSM activation at 49.8 / 50.2 Hz.

      Terms: cited.

      Regulation (EU) 2016/631, requirements for generatorsRfG

      Network code on requirements for grid connection of generators: frequency ranges generators must ride through.

      Used for: the 51.5 Hz upper limit in the game.

      Terms: EU law, © European Union, reuse authorised with acknowledgement.

      ENTSO-E, SAFA Policy on Emergency and Restoration

      Used for: Continental Europe's load‑shedding design and reconnection above 49.8 Hz.

      Terms: cited.

      NREL slides on the Iberian blackout

      National Renewable Energy Laboratory, 2025 (docs.nrel.gov 95103).

      Used for: system inertia of 2.3 s at 12:30, against a 2 s floor, used to calibrate the model.

      Terms: US government work, cited.

      REN, AEMET and EDMO on the "atmospheric" claim

      REN statement as reported by AFP and Euronews (April 2025); AEMET (Spanish weather agency) statement; European Digital Media Observatory fact‑check.

      Used for: the atmospheric‑vibration myth card.

      Terms: press and public statements, paraphrased.

      Maldita.es, citing REE

      Fact‑check on the solar share, 2025.

      Used for: solar at 51% at 12:30 on 22 April, which REE's own data reproduces (17,167 MW of about 33.7 GW).

      Terms: press, cited.

      Geist and Geist Mono

      Used for: the typefaces, served by Google Fonts.

      Licence: SIL Open Font License 1.1.

      Research brief behind this page, with every claim and its source: run-the-grid/RESEARCH.md. Data build: run-the-grid/build. Version 1, October 2026.